I-o-display-systems Basic I/O Product Manual de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 81
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
Setup & Installation 2
2-4(Vol.1)
BASIC I/Os can be networked together to obtain up to 4096 I/O points of data. These serial
networks can be either multidrop or repeat.
Figure 2-3 Multidrop V.S. Repeat networks
Multidrop:
Multidrop networks can be up to 5000 ft long end-to-end.
Each station is passively located on the network and represents one “Drop” or
load to the host communication driver.
A multidrop network will tolerate loss of power to any one station without
effecting the rest of the network..
RS-485 can only be multidrop
Signal boost may be necessary depending on line conditions and number of
drops.
Repeat:
Repeat networks can be as long as 5000 ft between each unit.
Each station plays an active role in communications to other units. If power is
removed from a unit in a repeat network, communications to units “downstream”
from it will be lost as well.
Vista de pagina 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 80 81

Comentarios a estos manuales

Sin comentarios